  Datasheet File OCR Text:
 EMC filters
3-line filters
for converters and power electronics
Rated current 180 to 1600 A
Series/Type: Date: B84143B*S080, S081 January 2006
EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet and the information contained therein without EPCOS' prior express consent is prohibited.
3-line filters for converters and power electronics
Power line filters for 3-phase systems Rated voltage 520/300 and 760/440 V AC Rated current 180 to 1600 A Construction
3-line filter Metal case
B84143B*S080, S081
Features

Optimized leakage current
Easy to install
Very compact design
Optimized for operation under full load
Low weight
Design complies with
EN 133200, UL 1283, CSA C22.2 No.8 UL, cUL approval Applications
Frequency converters for motor drives
Wind farms
Power supplies
Terminals
Busbars
Marking Marking on component: Manufacturer's logo, ordering code, frequency, rated voltage, rated current, rated temperature, climatic category, date code Minimum marking on packaging: Manufacturer's logo, ordering code
Please read Cautions and warnings and
Important notes at the end of this document.
2
01/06
3-line filters for converters and power electronics
Typical circuit diagram
LINE L1
L2 L3
B84143B*S080, S081
LOAD
L1' L2' L3'
SSB2008-L
Technical data and measuring conditions Rated voltage VR Type S080: Type S081: 520/300 V AC, 50/60 Hz 760/440 V AC, 50/60 Hz (Suitable for IT mains supply up to 560/320 V. See also Chapter "General", section 7.4)
Rated current IR Test voltage Vtest
Referred to 40 C ambient temperature (180 A filter at 60 C) Type ...S080: 2240 V DC, 2 s (line/line) 2720 V DC, 2 s (lines/case) Type ...S081: 3270 V DC, 2 s (line/line) 2890 V DC, 2 s (lines/case)
Overload capability (thermal) Leakage current lleak
1.5 * IR for 3 min per hour or 2.5 * IR for 30 s per hour Type ...S080: at 520 V AC, 50 Hz Type ...S081: at 760 V AC, 50 Hz UL 1283; CSA C22.2 No.8 (Type S080: 500/290 V; Type S081: 600/350 V)
Climatic category (IEC 60068-1) 25/100/21 (-25 C/+100 C/21 days damp heat test) Approvals
Please read Cautions and warnings and
Important notes at the end of this document.
3
01/06
3-line filters for converters and power electronics
Characteristics and ordering codes
VR AC V
B84143B*S080, S081
IR A 1801) 250 320 400 600 1000 1600
Ileak mA < 21 < 21 < 21 < 21 < 21 < 40 < 40 < 31 < 31 < 31 < 31 < 31 < 58 < 58
Rtyp 110 110 51 48 43 29 22 110 110 51 48 43 29 22
Approx. weight kg 5.0 5.0 7.2 7.5 7.8 18.5 24.5 5.0 5.0 7.2 7.5 7.8 18.5 24.5
Ordering code
Approvals
Type S080 520/300 B84143B0180S080 B84143B0250S080 B84143B0320S080 B84143B0400S080 B84143B0600S080 B84143B1000S080 B84143B1600S080 B84143B0180S081 B84143B0250S081 B84143B0320S081 B84143B0400S081 B84143B0600S081 B84143B1000S081 B84143B1600S081
500/290 V x x x x x x - x x x x x x - x x x x x x - x x x x x x -
Type
S0812) 1801) 250 320 400 600 1000 1600
600/350 V
760/440
x = approval granted
1) B84143B0180S080 and B84143B0180S081 referred to 60 C ambient temperature
Please read Cautions and warnings and
Important notes at the end of this document.
4
01/06
3-line filters for converters and power electronics
Dimensional drawings
B84143B0180S08*, B84143B0250S08* (180 A, 250 A)
140 303 303 o9 90
B84143B*S080, S081
20
110
10 2502 1450.5 6.6 L1 L2 L3 200 Marking LINE LOAD
10
1551
L1' L2' L3'
3
170
SSB2147-D
B84143B0320S08*, B84143B0400S08* (320 A, 400 A)
140 403 403 o11 90
25
116
76
2
15 2902 o12 L1 L2 L3 230 Marking LINE LOAD 1700.5
15
1651
L1' L2' L3'
5
190
SSB2148-L
Please read Cautions and warnings and
Important notes at the end of this document.
5
01/06
78.2
2
3-line filters for converters and power electronics
B84143B0600S08* (600 A)
140 403 403 o11
30 116 78.2
B84143B*S080, S081
90
15 2902 o12 L1 L2 L3 230 Marking LINE LOAD 1700.5
15
1651
L1' L2' L3'
5
190
SSB2149-U
B84143B1000S08* (1000 A)
210 523 523 o14 142
40
140
2
3702.5 o12 L1 L2 L3 Marking LINE LOAD L3' 2401
L1'
8
2351
L2'
300
260
SSB2150-X
Please read Cautions and warnings and
Important notes at the end of this document.
6
01/06
2.5
20
20
89.7
3-line filters for converters and power electronics
B84143B1600S08* (1600 A)
923
B84143B*S080, S081
923 o14
50
40 20 89,7 2,5 o12 L1 L2 L3 Marking LINE LOAD L3' 2401 4503
40 20
10
L1'
2351
210
142
L2'
140
3001,5
SSB2013-M
Please read Cautions and warnings and
Important notes at the end of this document.
7
01/06
260
3-line filters for converters and power electronics
Insertion loss (typical values at Z = 50 ) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) Filters for 180 A and 250 A
100 B84143B0180S08* dB B84143B0250S08* 80
SSB2003-F
B84143B*S080, S081
Filters for 320 A and 400 A
100 B84143B0320S08* dB B84143B0400S08* 80
SSB2004-N
60
60
40
40
20
20
0 10 4
10 5
10 6
10 7
Hz 10 8 f
0 10 4
10 5
10 6
10 7
Hz 10 8 f
Filters for 600 A
100
SSB2005-W
Filters for 1000 A
100 dB 80 B84143B1000S08*
SSB2006-5
dB
B84143B0600S08*
80
60
60
40
40
20
20
0 10 4
10 5
10 6
10 7
Hz 10 8 f
0 10 4
10 5
10 6
10 7
Hz 10 8 f
Please read Cautions and warnings and Important notes at the end of this document.
8
01/06
3-line filters for converters and power electronics
Insertion loss (typical values at Z = 50 ) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) Filters for 1600 A
100 dB B84143B1600S08* 80
SSB2007-D
B84143B*S080, S081
60
40
20
0 10 4
10 5
10 6
10 7
Hz 10 8 f
Please read Cautions and warnings and
Important notes at the end of this document.
9
01/06
EMC filters Cautions and warnings
Important information Please read all safety and warning notes carefully before installing the EMC filter and putting it into operation (see ). The same applies to the warning signs on the filter. Please ensure that the signs are not removed nor their legibility impaired by external influences. Death, serious bodily injury and substantial material damage to equipment may occur if the appro priate safety measures are not carried out or the warnings in the text are not observed. Using according to the terms The EMC filters may be used only for their intended application within the specified values in low voltage networks in compliance with the instructions given in the data sheets and the data book. The conditions at the place of application must comply with all specifications for the filter used. Warnings
It shall be ensured that only qualified persons (electricity specialists) are engaged on work such

as planning, assembly, installation, operation, repair and maintenance. They must be provided with the corresponding documentation. Danger of electric shock. EMC filters contain components that store an electric charge. Danger ous voltages can continue to exist at the filter terminals for longer than five minutes even after the power has been switched off. The protective earth connections shall be the first to be made when the EMC filter is installed and the last to be disconnected. Depending on the magnitude of the leakage currents, the particular specifications for making the protective-earth connection must be observed. Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequen cies that may cause resonances etc. can lead to destruction of the filter housing. EMC filters must be protected in the application against impermissible exceeding of the rated currents by suitable overcurrent protective.
10
01/06
EMC filters Important notes
The following applies to all products named in this publication: 1. Some parts of this publication contain statements about the suitability of our products for certain areas of application. These statements are based on our knowledge of typical requirements that are often placed on our products in the areas of application concerned. We nevertheless expressly point out that such statements cannot be regarded as binding statements about the suitability of our products for a particular customer application. As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them than the customers themselves. For these reasons, it is always ultimately incumbent on the customer to check and decide whether an EPCOS product with the properties described in the product specification is suitable for use in a particular customer application. 2. We also point out that in individual cases, a malfunction of passive electronic components or failure before the end of their usual service life cannot be completely ruled out in the current state of the art, even if they are operated as specified. In customer applications requiring a very high level of operational safety and especially in customer applications in which the malfunction or failure of a passive electronic component could endanger human life or health (e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of suitable design of the customer application or other action taken by the customer (e.g. installation of protective circuitry or redundancy) that no injury or damage is sustained by third parties in the event of malfunction or failure of a passive electronic component. 3. The warnings, cautions and product-specific notes must be observed. 4. In order to satisfy certain technical requirements, some of the products described in this publication may contain substances subject to restrictions in certain jurisdictions (e.g. because they are classed as "hazardous"). Useful information on this will be found in our Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more detailed questions, please contact our sales offices. 5. We constantly strive to improve our products. Consequently, the products described in this publication may change from time to time. The same is true of the corresponding product specifications. Please check therefore to what extent product descriptions and specifications contained in this publication are still applicable before or when you place an order. We also reserve the right to discontinue production and delivery of products. Consequently, we cannot guarantee that all products named in this publication will always be available. 6. Unless otherwise agreed in individual contracts, all orders are subject to the current version of the "General Terms of Delivery for Products and Services in the Electrical Industry" published by the German Electrical and Electronics Industry Association (ZVEI). 7. The trade names EPCOS, EPCOS-Jones, Baoke, CeraDiode, CSSP, MLSC, PhaseCap, PhaseMod, SIFI, SIKOREL, SilverCap, SIMID, SIOV, SIP5D, SIP5K, UltraCap, WindCap are trademarks registered or pending in Europe and in other countries. Further information will be found on the Internet at www.epcos.com/trademarks.
11
01/06


▲Up To Search▲   

 
Price & Availability of B84143B0320S080

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X